Appendix J: Canadian Applications - Honeywell Fire-Lite Alarms ES-200X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-200X:
Table of Contents

Advertisement

The ES-200XC is supplied standard with the DP-ES-R Dress Panel for Canadian applications.
When installing and programming the FACP, the Canadian Option must be set to ON prior to any other panel programming (refer to
"Canadian Option" on page 79 of the Programming Section of this manual).
At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary operator interface. Wiring to the ANN-
LED must be in metal conduit and must be connected to the FACP's Primary ANN-BUS.
If remote indicators are desired, they must be connected to the Secondary ANN-BUS circuit.
The installer must write in the Date of Final Assembly on the Master Marking and Warranty Label located on the FACP backbox
door.
Positive Alarm Sequence (PAS), the Pre-Signal option, and the Auto-Silence option are not available for Canadian applications.
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
The F2 function key is automatically configured to perform a two-stage bypass when pressed which advances NAC coding directly
to the second stage alarm.
The F3 function key is automatically configured to perform an automatic alarm signal cancel in two-stage NAC operation. This
prevents the NAC from advancing to the second-stage alarm.
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
AlarmNet supervision settings for panels communicating by Cellular-only or Ethernet-only method are fixed at 3 minutes and
cannot be changed regardless of programming selection.
156

Appendix J: Canadian Applications

Optional Secondary ANN-BUS (data on
connector TB10, power on TB11
Terminals 5&6 with power programmed
as non-resettable)
Primary ANN-BUS (data
on connector TB9, non-
resettable power on
TB11 Terminals 1&2) in
metal conduit (adjacent
to FACP)
ANN-LED
FACP
FIRE SYSTEM
ALL
SYSTEM
ACTIVE
CALL
CONTROL
1
13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
23
12
24
FI
LIT
®
AL
by Honeywell
optional
ECC-50/100
audio system
Figure J.1 FACP Minimum Configuration - Single ANN-LED
ANN-LED
ANN-100
ANN-I/O
ANN-S/PG
ANN-RLY
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-200xc

Table of Contents