Remote Fire Annunciator - Honeywell Fire-Lite Alarms ES-200X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms ES-200X:
Table of Contents

Advertisement

Installation
7.
After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any
excess wire pushed back through hole into electrical box
ANN-BUS Device
The following table shows the ANN-80 connections to the ES-200X.
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must be added to the system via FACP
programming. Refer to the programming section titled "ANN-BUS Setup" on page 90 in this manual for detailed programming informa-
tion.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate a trouble condition by NOT turning
on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds.
Note that the FACP will provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-80
at the FACP.
ANN-100 Remote Fire Annunciator
Specifications
Operating Voltage: 24 VDC
Current
– Standby: 20 mA
– Alarm: 25 mA
Ambient Temperature: 32°F to 120°F (0°C to 49°C)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface or Flush-mount
Dimensions: 12-1/4"W x 11-1/2"H x 7/8"D (31.1 cm W x 29.2 cm H x 2.2 cm D)
For indoor use in a dry location only
The following table shows the ANN-100 connections to the ES-200X.
38
TB1
4 3 2 1
Figure 2.20 ANN-80 Wiring to FACP
ES-200X
Terminal GND (-) on TB11
Terminal PWR (+) on TB11
Terminal Data (A) on TB9
Terminal Data (B) on TB9
ES-200X
Terminal GND (-) on TB11
Terminal PWR (+) on TB11
Terminal Data (A) on TB9
Terminal Data (B) on TB9
ANN-BUS and power wiring are
supervised and power-limited
Primary
+
-
ANN-BUS
ES-200X
ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
ANN-100 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Optional Module Installation
24 VDC
nonresettable