Master Programming Level
Ack Switch
Sil Switch
Reset Switch
Drill Switch
PAS Bypass
HVAC RESTART
Drill Switch AR
Wireless Gateway
1
programmed by the installer for Class B operation and isolator modules must be employed on each
non-fire branch of the SLC as shown in the SLC Wiring Manual (document number 51309). Fire and
non-fire devices must not be used on the same SLC branch. For UL2017 compliance, The ANN-LED
annunciator must be used to indicate the active, dedicated zone or device
2
3
page 146.
Pre-signal
EDIT MONITOR
1=PRE-SIGNAL
WIRELESS
Edit Monitor Screen #3
Wireless
The Wireless selection will update automatically if the system recognizes a wireless device. If the module is wireless, the display reads
Wireless Yes. If the module is wired, the display will read Wireless No. Fore more information on the SWIFT wireless network, refer to
the SWIFT manual, #LS10036-000FL-E.
Walktest
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
000    
Edit Monitor Screen #4
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4
displays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the three digit number corresponding to the zone that is
to be assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones
can be left blank or programmed as general alarm zones Z000. When all desired changes have been made, press the Enter key to store the
zone assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
EDIT MONITOR
1=NOUN/ADJECTIVE
2=DESCRIPTION

Edit Monitor Screen #5
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
3
Switch (see note 2)
2
Acts like panel Drill Key, nonlatching (tracking)
SWIFT gateway needs this type to display wireless troubles at the FACP
Combination systems employing these non-fire monitor types require the SLC loop to be
For entries ending in AR, AR refers to AutoResettable.
For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor Module Operation" on
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-
signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal
NO
NO
No. Refer to"Presignal" on page 112 for additional information.
The Walktest feature allows one person to test the system devices without the necessity of manually reset-
YES
ting the control panel after each device activation. To enable devices, which are connected to a monitor
module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads
Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No.
Refer to "Walktest" on page 114 for additional information.
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module
currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following
screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Table 3.1 Monitor Types
ZONE ASSIGNMENT
Z000
Zone Assignment Screen
Noun/Adjective Screen
Programming
63