Automatic Audio Panel Control

2.8.6 ECC-FFT Firefighter Telephone
The ECC-FFT connects from TB11 (non-resettable aux power) on the FACP to the DC Power input on the ECC-FFT board.
2.8.7 W-GATE Wireless Gateway
The W-GATE connects to the FACP's SLC connection at TB10. The W-GATE can be powered by either the SLC or an external 24 VDC
power source. A maximum of 100 wireless devices can be used in the system. Refer to the SWIFT® Smart Wireless Integrated Fire
Technology Manual for more information.
NOTE: The W-GATE, as part of the wireless network, has been tested for compliance with the Federal Communications Commission
(FCC) requirements of the United States Government. It has not been evaluated for use outside the USA. Use of this system outside the
USA is subject to local laws and rules to which this product may not conform. It is the sole responsibility of the user to determine if this
product may be legally used outside the USA.
2.9 Automatic Audio Panel Control
The FACP annunciator bus serves as the "FACP Data Bus" to the ECC-50/100 or ACC-25/50 audio system. User programming is
required to set up the operation of the audio system. To set up the annunciator bus, refer to Section 2.8.4 on page 33. The annunciator
protocol, ANN-Bus, must be selected and enabled.
The FACP will automatically detect the audio system connection during annunciator "auto-configuration". No ANN-Bus address selec-
tion is necessary at the FACP.
Once the FACP can communicate with the audio system, FACP zones Z33 through Z56 become automatically dedicated as output zones
for speaker circuits 1 through 24 respectively. FACP zone Z32 is dedicated to turn on all speaker circuits. FACP programming allows
association between any addressable SLC input device (module, detectors) with any of the speaker circuits. In addition 1 of 14 messages
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018