Parameters
Conductor cross-section
Reverse voltage protection

4.4.5 Electrical Safety

Property
Insulation resistance
Test voltage
Min. creepage distance
Requirements
• Use of PELV/SELV power supplies
• When SELV power supplies are used: SELV power supplies with supply via the same
network phase
• If PELV (Protective Extra Low Voltage) power supplies are used: PELV (Protective Ex-
tra Low Voltage) power supplies with a secondary power supply connection to the
common reference point

4.4.6 Environmental Conditions

Property
Surrounding air temperature (operation)
Surrounding air temperature (storage)
Maximum temperature change
Relative humidity (operation)
Pollution degree
Operating altitude
Overvoltage category
Protection type
Protection class
Vibration resistance
Shock resistance

4.4.7 Communication

Property
Communication Interfaces
Protocols
20
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
Value
additional modules are connected to X32 (PWR OUT),
it may be necessary for the maximum total current to
be monitored with external power supply management.
Maximum current: Observe derating as a function of
surrounding air temperature.
2
For UL-compliant use: 2.5 mm
Yes
Table 13: Electrical Safety
Value
60 VDC
550 VAC RMS
0.7 mm
Table 14: Environmental Conditions
Value
–25 °C ... +70 °C
–40 °C ... +80 °C
3 K/min
5 % ... 95 %
3 (EN 60664-1)
0 ... 2000 m
II (EN 60664-1)
IP67 (EN 60529)
III (EN 61140)
5g (IEC 60068-2-6)
50g (IEC 60068-2-27)
Table 15: Communication
Value
ETHERNET, Bluetooth®
EtherCAT®, HTTP, OPC UA
765-1205/0100-0000

Advertisement