Commissioning
10.3.3.1.6 Read Statistics
The OPC UA server provides nodes with statistical information. For example, the OPC
UA client can read out the maximum measured current on pin 1 of a port in the MaxCur-
rentPin1 node. The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > Statistics > Current / Temperature / Voltage
The following table lists port-specific statistical information:
Node Name
MaxCurrentPin1,
MaxCurrentPin2,
MaxCurrentPin4
MinCurrentPin1,
MinCurrentPin2,
MinCurrentPin4
MaxTemperature-
Pin1,
MaxTemperature-
Pin2,
MaxTemperature-
Pin4
MinTemperature-
Pin1,
MinTemperature-
Pin2,
MinTemperaturePin4
MaxVoltagePin1,
MaxVoltagePin2,
MaxVoltagePin4
MinVoltagePin1,
MinVoltagePin2,
MinVoltagePin4
78
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
Node Class
Access
Variable
Read
Variable
Read
Variable
Read
Variable
Read
Variable
Read
Variable
Read
765-1205/0100-0000
Table 53: Port Specific Statistical Information
Description
Maximum current on pin 1, pin 2 or pin 4
since the value was reset; unit: mA
Minimum current on pin 1, pin 2 or pin 4
since the value was reset; unit: mA
Maximum temperature on pin 1, pin 2 or
pin 4 since the value was reset; unit: °C
Minimum temperature on pin 1, pin 2 or
pin 4 since the value was reset; unit: °C
Maximum voltage on pin 1, pin 2 or pin 4
since the value was reset; unit: mV
Minimum voltage on pin 1, pin 2 or pin 4
since the value was reset; unit: mV