Commissioning

10.3.1.3.2 Displaying Measured Values and Information on Connected Sensors/Actuators

The Information tab shows the following information:
• The measured values and states of the port diagnostics
• The information on connected sensors/actuators
Displaying Pin- and Port-Specific Measured Values and States
The Information tab shows the following current measured values for each of pin 1, pin 2
and pin 4 of the selected port:
• Temperature of the pin, measured in °C
• Voltage on the pin, measured in volts
• Current flowing through the pin, measured in amperes
• State of the connection pin
States of the Connection Pin
The possible states of the connection pin are:
• OK
• Short circuit
• Module-internal overload protection has triggered
• Module-internal overtemperature protection has triggered
• Module-internal overvoltage protection has triggered
• Overcurrent
• Undercurrent
• Overtemperature
• Undertemperature
• Overvoltage
• Undervoltage
• Module-internal watchdog timer has elapsed
58
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
765-1205/0100-0000
Figure 11: Information Tab, Port XX Menu Item