Power Supply; Table 12 Power Supply - WAGO 765-1205/0100-0000 Manual

8-channel digital input/output; ethercat; 24 v dc; 2.0 a;
Table of Contents

Advertisement

765-1205/0100-0000
Property
Circuit
Voltage drop through high-side path
Self-protection
Maximum capacitive load
Maximum inductive load
Indicators
Diagnostics
Actuator/Sensor Power Supply
Output voltage
Current
Circuit
Self-protection
Voltage drop through high-side path
Maximum capacitive load
Maximum inductive load
Diagnostics (1L+, 2L+)

4.4.4 Power Supply

Parameters
Supply voltage, 1L, 2L
Undervoltage warning, 1L, 2L
Overvoltage warning, 1L, 2L
Module power consumption
Power consumption of supply connections
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
Value
High-side driver
The digital output is not resistant to reverse power
feeding.
The input voltage must not exceed the supply voltage.
Less than 250 mV
Overcurrent, overload, overtemperature and overvolt-
age
100 μF parallel to 12 Ω; 10 Hz
1.15 H / 2 A; 0.2 Hz; DC13
On/off status LED
Events: overcurrent, overload and overtemperature
24 VDC
Port X01 to X04: 1L powered
Port X05 to X08: 2L powered
Maximum 4.0 A per channel
High-side driver
The 1L+/2L+ output is not resistant to reverse power
feeding.
The input voltage must not exceed the supply voltage.
Overcurrent, overload, overtemperature and overvolt-
age
Less than 200 mV
1000 µF parallel to 24 Ω; 0.1 Hz
470 µF parallel to 12 Ω; 0.1 Hz
220 µF parallel to 6 Ω; 0.1 Hz
1.15 H / 2 A; 0.2 Hz; DC13
Events: overcurrent, overload, overtemperature and
overvoltage
Value
24 VDC, –25 %/+30 % (18 VDC ... 31.2 VDC)
Voltages above 34 V can permanently damage the de-
vice.
Voltages below approx. 11 V lead to device reset.
18.0 V (± 5 % at 25 °C) message On,
18.3 V (± 5 % at 25 °C) message Off
30.0 V (± 5 % at 25 °C) message On,
29.7 V (± 5 % at 25 °C) message Off
1L: 110 mA (at 24 VDC)
2L: 5 mA (at 24 VDC)
Max. 16 A; ensure external limitation or use fuses in
the cables.
The maximum total current of the device, including
transmission between the power supply connections,
must not exceed 16 A for both 1L and 2L individually. If
Properties
Table 12: Power supply
19