Using the two wires of an 10 AWG cable running from the DC power
distribution unit, connect the black wire into the -48 VDC terminal block
and the red wire to the RTN terminal block.
A
I
DDITIONAL
NFORMATION
DC power
A 10 AWG cable must be used to connect the mains with the RealPres-
ence Collaboration Server (RMX) 4000 DC PEM.
The supply wires for DC version must be terminated using quick
connectors.
Extension cords may not be used.
The center PEM slot/module is fitted with a blank panel and the slot cannot be
used on a system with DC Voltage.
6.
Connect the green or green-yellow wire to the system single-point
M6x15 "Ground" bolt
A
I
DDITIONAL
NFORMATION
The rating of the protective earthing conductor should be a minimum of 10 AWG.
If the unit is rack mounted, the single-point ground on the MCU must be
connected to the rack with a single conductor and fixed as to prevent loos-
ening. When using bare conductors, they must be coated with an appropriate
antioxidant compound before crimp connections are made. Tinned,
solder-plated or silver plated connectors do not have to be prepared in this
manner.
7.
Replace the transparent plastic cap on the terminal block.
P
R
OLYCOM
:
:
Protective earthing conductor
P
R
P
C
OLYCOM
EAL
RESENCE
OLLABORATION
P
C
EAL
RESENCE
OLLABORATION
S
G
S
ERVER
ETTING
TARTED
S
.8.6
ERVER V
G
UIDE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Realpresence 2000Realpresence 4000

Table of Contents