Use a USB connector, serial port, or the Ethernet connector on the personal computer for connection.
 Related parameters for connection using CC-Link IE TSN (for FR-A800/
FR-F800 inverter with FR-A8NCG in it)
• For details on CC-Link IE TSN communication, refer to the CC-Link IE TSN Function Manual or FR-A8NCG Instruction
Manual.
Pr.
*1*2
434
IP address 1
N700
*1*2
435
IP address 2
N701
*1*2
436
IP address 3
N702
*1*2
437
IP address 4
N703
*1*2
438
Subnet mask 1
N710
*1*2
439
Subnet mask 2
N711
*1*2
440
Subnet mask 3
N712
*1*2
441
Subnet mask 4
N713
*1*2
1442
IP filter address 1 (Ethernet)
N760
*1*2
1443
IP filter address 2 (Ethernet)
N761
*1*2
1444
IP filter address 3 (Ethernet)
N762
*1*2
1445
IP filter address 4 (Ethernet)
N763
*1*2
IP filter address 2 range specification
1446
(Ethernet)
N764
*1*2
IP filter address 3 range specification
1447
(Ethernet)
N765
*1*2
IP filter address 4 range specification
1448
(Ethernet)
N766
*1*2
1459
Clock source selection
N746
*1
The setting is applied after an inverter reset or power-ON.
60
1. OUTLINE
1.4 Connection and parameter setting
USB connector,
Serial port,
Ethernet connector
Personal computer
(FR Configurator2)
Ethernet
connector
Inverter
Initial
Name
value
0 (192
0 (168
0 (50
0 (2
0 (255
0 (255
0 (255
0
0
0
0
0
9999
9999
9999
0
Computer to programmable controller
(CPU module, Ethernet module)
Programmable controller
(Ethernet module) to inverter
Ethernet
cable
Up to 64 or
Hub
120 inverters
Setting range
*3
0 to 255
)
*3
0 to 255
)
Enter the IP address of the inverter to be connected
to CC-Link IE TSN.
*3
0 to 255
)
*3
0 to 255
)
*3
0 to 255
)
*3
0 to 255
)
Enter the subnet mask of the network to which the
inverter belongs.
*3
0 to 255
)
0 to 255
0 to 255
0 to 255
0 to 255
Set the range of connectable IP addresses for the
network devices.
0 to 255
(When Pr.1442 to Pr.1445 = "0 (initial value)", the
function is invalid.)
0 to 255, 9999
0 to 255, 9999
0 to 255, 9999
The internal clocks of connected devices on the CC-
0 to 2
Link IE TSN Network can be synchronized (real time
clock function).
Description