 Related parameter list
• 800 series
Pr.
Name
117
PU communication station number
N020
118
PU communication speed
N021
N022
PU communication data length
N023
PU communication stop bit length
PU communication stop bit length / data
119
length
120
PU communication parity check
N024
122
PU communication check time interval
N026
123
PU communication waiting time setting 9999
N027
*1*2
PU mode operation command source
551
selection
D013
*1
Pr. 551 is always write-enabled.
*2
The setting range depends on the inverter. For the details, refer to the Instruction Manual of the inverter.
Initial
Setting range
value
Inverter station number specification.
0
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
Set the communication speed.
48, 96, 192,
The setting value × 100 equals the communication
192
384, 576, 768,
speed.
1152
For example, if 192 is set, the communication speed is
19200 bps.
0
Data length 8 bits
0
1
Data length 7 bits
0
Stop bit length 1 bit
1
1
Stop bit length 2 bits
0
Stop bit length 1 bit
1
Stop bit length 2 bits
1
10
Stop bit length 1 bit
11
Stop bit length 2 bits
0
Without parity check
2
1
With parity check at odd numbers
2
With parity check at even numbers
0
PU connector communication is disabled.
Set the communication check time interval.
If a no-communication state persists for the
9999
0.1 to 999.8 s
permissible time or longer, the inverter output is shut
off. (The operation depends on the Pr.502 setting.)
9999
No communication check (signal loss detection)
Set the delay between data transmission to the
0 to 150 ms
inverter and response.
9999
Set with communication data.
RS-485 terminals are the command interface enabled
1
in the PU operation mode.
The PU connector is the command interface enabled
2
in the PU operation mode.
The USB connector is the command interface enabled
3
in the PU operation mode.
The operation panel is the command interface enabled
9999
4
in the PU operation mode.
The Ethernet connector is the command interface
5
enabled in the PU operation mode.
USB automatic recognition
Basically, the operation panel (PU connector) is the
9999
command interface. When the USB connector is used,
it is the command interface.
Description
Data length 8
bits
Data length 7
bits
1. OUTLINE
1.4 Connection and parameter setting
1
2
3
4
5
6
7
8
9
10