Mitsubishi Electric MELSOFT FR Configurator2 Instruction Manual page 56

Table of Contents

Advertisement

Pr.
Name
549
Protocol selection
N000
*3
PU mode operation command source
551
selection
D013
999
Automatic parameter setting
E431
*1
Set Pr.549 = "0" (Mitsubishi inverter (Computer link) protocol).
*2
The setting is available only for the FR-F800 series.
*3
Pr.551 can be always written regardless of the operation mode.
*4
The read value is always "9999".
• 700 series
Pr.
Name
117
PU communication station number
118
PU communication speed
PU communication stop bit length / data
119
length
120
PU communication parity check
121
PU communication retry count
Initial
Setting range
value
*1
Mitsubishi inverter protocol (computer link)
0
0
1
MODBUS RTU protocol
*2
BACnet MS / TP protocol
2
The RS-485 terminals are the command interface
1
enabled in the PU operation mode.
The PU connector is the command interface enabled
2
in the PU operation mode.
The USB connector is the command interface in the
3
PU operation mode.
4
The operation panel is the command interface enabled
9999
in the PU operation mode.
The Ethernet connector is the command interface in
5
the PU operation mode.
USB automatic recognition
Basically, the operation panel (PU connector) is the
9999
command interface. When the USB connector is used,
it is the command interface.
1
Standard PID setting
2
Extended PID setting
GOT initial setting (PU
10
connector)
GOT initial setting (RS-485
11
terminals)
GOT initial setting (PU
*4
12
9999
connector)
GOT initial setting
13
Automatic setting (RS-485
terminals)
20
50 Hz rated frequency
21
60 Hz rated frequency
9999
No action
Initial
Setting range
value
Inverter station number specification.
0
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
Set the communication speed.
48, 96, 192,
The setting value × 100 equals the communication
192
384, 576, 768,
speed.
1152
For example, if 192 is set, the communication speed is
19200 bps.
0
Stop bit length 1 bit
1
Stop bit length 2 bits
1
10
Stop bit length 1 bit
11
Stop bit length 2 bits
0
Without parity check
2
1
With parity check at odd numbers
2
With parity check at even numbers
Set the permissible number of retries for unsuccessful
data reception. If the number of consecutive errors
0 to 10
exceeds the permissible value, the inverter output is
1
shut off.
Even if a communication error occurs, the inverter will
9999
not trip.
Description
GOT side model
selection: FR 500/700/
800, sensorless servo
GOT side model
selection: FR 800
Description
Data length 8 bits
Data length 7 bits
1. OUTLINE
1.4 Connection and parameter setting
1
2
3
4
5
6
7
8
9
10
55