Error code (HEX)
0x80010029
0x8001002A
0x8001002B
0x8001002C
0x8001002D
0x8001002E
0x80010101
0x80010102
0x8001101B
0x80011026
0x80020001
0x80020002
0x80020003
0x80020004
0x80020005
0x80020006
0x80020007
0x80020008
220
4. TROUBLE INDICATION
4.1 Error code
Error message
The remote password is not
correct.
Enter the password again after 1
minutes.
Enter the password again after 5
minutes.
Enter the password again after
15 minutes.
Enter the password again after
60 minutes.
Enter the password again after a
while.
Communication was not
established with the inverter
within the timeout time.
The data received by the
computer contains incorrect
data.
Not specified as the command
source.
Access is disabled by exclusion
control.
The communication line cannot
be opened.
The parameter outside the
setting range cannot be written.
An unexpected error occurred in
S/W.
The reception data could not be
acquired.
Possible cause
A remote password is set for a
device connected via Ethernet, but
a different password was entered.
The remote password was entered
before the specified interval has
passed.
• The setting values in Pr.122 PU
communication check time
interval, Pr.336 RS-485
communication check time
interval, Pr.548 USB
communication check time
interval, and Pr.1432 Ethernet
communication check time
interval (Pr.852 for FR-E700-
NE) are too small.
• Electromagnetic interference.
• Cable breakage/damage.
• The personal computer port is set
invalid or the port is broken.
• Power source was changed from
the USB power supply or the 24 V
external power supply to the main
circuit power supply.
• The Pr.124 PU communication
CR/LF selection and Pr.341 RS-
485 communication CR/LF
selection settings are different
with the software settings.
• Electromagnetic interference.
• Inverter reset (or power-OFF)
• Cable breakage.
Appears if parameter writing or
operation mode change is
attempted through the unspecified
command interface.
More than one device is trying to
access the inverter.
Invalid communication data type.
An out-of-range value was written
to the parameter.
Please contact your sales representative.
The sampling data could not be
obtained by the high speed
sampling.
Countermeasure
Enter the correct password again.
Enter the correct password at the
specified intervals.
Enter the remote password at the
specified intervals.
• Set a larger value or "9999" in
Pr.122 PU communication check
time interval, Pr.336 RS-485
communication check time
interval, Pr.548 USB
communication check time
interval, and Pr.1432 Ethernet
communication check time
interval (Pr.852 for FR-E700-NE).
• Set a larger value for the timeout
setting of the software.
• Connect or replace the cable.
• Activate the port using Device
Manager, or replace the port.
• Check the status of the inverter.
• Match the Pr.124 PU
communication CR/LF selection
and Pr.341 RS-485
communication CR/LF selection
settings with the software settings.
• Set a larger value in Pr.121 PU
communication retry count and
Pr.335 RS-485 communication
retry count.
• Do not reset the inverter or turn OFF
the inverter power during
communication.
• Replace the cable.
Check the command source.
Avoid device access conflict.
Check the communication settings.
Set a value within the setting range,
and enter the setting.
If a writing error occurs even if a value
within the setting range is written,
check for the writing requirements for
each parameter. For the details on the
writing requirements, refer to the
Instruction Manual of the inverter.
• Close other applications.
• Set a larger value for the mask
count.
• Decrease the number of sampling
channels.