Technical Data; Electrical Data - Siemens 8DA10 Series Installation And Operating Instructions Manual

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Complete switchgear
Electrical data, filling pressure, temperature for single-busbar switchgear
Rated insulation level
Rated frequency f
r
1
Rated normal current
I
r
Filling pressure (pressure values
at 20 °C)
Ambient air temperature T
Degree of protection
1
The rated normal currents apply to ambient air temperatures of max. +40 °C.
The 24-hour mean value is max. +35 °C (according to IEC 62271-1 and IEC 62271-200).
2
Depending on the secondary equipment used
3
Depending on the design option
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
17

Technical data

17.1

Electrical data

Rated voltage U
r
Rated short-duration power-frequency withstand voltage U
- phase-to-earth, open contact gap
- across the isolating distance
Rated lightning impulse withstand voltage U
- phase-to-earth, open contact gap
- across the isolating distance
for the busbar
Rated filling level
(absolute) for
pre
busbar
Minimum functional level p
me
(absolute)
Operation without secondary
equipment
Operation with secondary equipment
for storage/transport, also with
3
secondary systems
for parts of the primary circuit under high
voltage
Switchgear enclosure
Low-voltage compartment
kV
12
24
d
kV
28
50
kV
32
60
p
kV
75
125
kV
85
145
Hz
50/60
50/60
A
1250
1250
A
2000
2000
A
2500
2500
A
3150
3150
A
4000
4000
A
5000
5000
kPa
70/120
kPa
50/100
°C
-25 to +55
2
°C
-5/-25 to +55
°C
-25 to +55
°C
-40 to +70 (option)
IP 65
3
IP 3XD/IP 31D
IP 31D/IP 41
Description
36
40.5
70
85
80
90
170
185
195
220
50/60
50/60
1250
1250
2000
2000
2500
2500
3150
3150
4000
4000
5000
5000
31/214