Siemens 8DA10 Series Installation And Operating Instructions Manual page 36

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Description
Characteristics of gas
pressure - temperature
Gas leakage rate
36/214
Busbar housing
Rated busbar current
Rated lightning impulse withstand voltage
Rated short-duration power-frequency
withstand voltage
Rated functional level
1
Min. functional level
Signal "pressure low"
Signal "pressure very low"
Max. functional level
Signal "pressure rising"
1
Min. functional level at which the rated insulation levels are accomplished.
Circuit-breaker housing
Rated busbar current
Rated lightning impulse withstand voltage
Rated short-duration power-frequency
withstand voltage
Rated functional level
1
Min. functional level
Signal "pressure low"
Signal "pressure very low"
Max. functional level
Signal "pressure rising"
1
Min. functional level at which the rated insulation levels are accomplished.
Fig. 16:
Characteristics of gas pressure as a function of
temperature
The characteristics of the gas pressures as a function of temperature show the behavior of
the SF
gas at different gas filling levels depending on the ambient air temperature.
6
Depending on the age and configuration of the switchgear, there may be deviations from
the characteristics shown above.
The gas leakage rate is < 0.1% per year (referred to the absolute gas pressure).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
A
1250
2000
2500
5000
kV
≤ 170
> 170
kV
≤ 70
> 70
kPa
70
kPa
50
kPa
50
kPa
40
kPa
120
kPa
120
A
≤ 1250
kV
≤ 170
> 170
kV
≤ 70
> 70
kPa
70
kPa
50
kPa
50
kPa
40
kPa
120
kPa
120
3150
4000
all
all
120
100
100
90
180
180
> 1250
all
all
120
100
100
90
180
180
120 kPa/20 °C
70 kPa/20 °C