Switching operations for busbar connection with three-position
disconnector
Connecting the busbar to the feeder
1
Initial situation
3
Switch the three-position disconnector to CLOSED
position (insert the operating lever for the
DISCONNECTING function and turn 180°
clockwise).
Disconnecting the busbar from the feeder
1
Initial situation
3
Switch the three-position disconnector to OPEN
position (insert the operating lever for the
DISCONNECTING function and turn 180° counter-
clockwise).
2
Push the control gate to the left.
4
Remove the operating lever for the
DISCONNECTING function.
The control gate returns to its initial position.
2
Push the control gate to the left.
4
Remove the operating lever for the
DISCONNECTING function.
The control gate returns to its initial position.