Technical Data; Digital Output Module With Rotary Coding Switch - Siemens SENTRON VL Series System Manual

Circuit breakers with communication capability - profibus
Hide thumbs Also See for SENTRON VL Series:
Table of Contents

Advertisement

3.5.2.2

Technical data

The table below contains the technical data of the digital input module on the CubicleBUS:
Table 3- 16
Operating voltage on the CubicleBUS min./max. (V)
Current consumption from the CubicleBUS min./max. (mA)
Number of isolated channels per digital input module
Voltage value for reliable detection of a "1" signal (V)
Current consumption per input at a "1" signal (mA)
Voltage value for reliable detection of a "0" signal (V)
Current consumption per input at a "0" signal (mA)
Maximum number of modules possible on one CubicleBUS
Power loss min./max. (W)
Dimensions W/H/D (mm)
Weight (kg)
Temperature range (°C)
3.5.3

Digital output module with rotary coding switch

Six binary information items about the switch status (alarms and tripping operations) can be
output via the digital output module to external signaling devices (e.g. indicator lights, horns),
or used for selective shutdown of other plant units (e.g. frequency converters).
The switch position on the left selects the events in the adjacent dark-gray field, and the
switch position on the right selects the events in the adjacent light-gray field.
Figure 3-18
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
Technical data of the digital input module
Digital output module
3WL air circuit breakers
3.5 External CubicleBUS modules
19.2 / 28.8
29 / 43
6
> 16 V
7.5
< 1 V
0
2
0.72 / 0.94
70 / 86 / 95
0.223
-20 / 60
69

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents