De-earthing the voltage transformers
1
Initial situation
3
➭
Switch the three-position disconnector from
EARTHED to OPEN position (insert the operating
lever for the READY-TO-EARTH function and turn
180° counter-clockwise).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Push the control gate to the right.
4
➭
Remove the operating lever for the READY-TO-
EARTH function.