861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
31

Installation of rear walls of switchgear

Environmental damages due to escaping SF
If panels are filled with SF
cross members.
➭ Do not remove the busbar housing covers.
➭ Undo just one bolt at the busbar housing cover at a time.
➭ Fasten the fixing cross members at the retainers and the busbar housings using
2 bolts M8x30 each. Tightening torque: 20 Nm.
Mounting position for intermediate panels or
end panels
Fig. 164: Mounting fixing cross members on busbar housings
Fixing cross members for right and left end panels
The fixing cross member for intermediate panels is identical with the fixing cross member for end panels.
If a higher busbar housing with disconnectable feeder to the top was mounted, turn the fixing cross
member by 180°.
Switchgear front
CAUTION
gas
6
gas, prevent the escape of SF
6
Mounting position turned by 180° for intermediate
panels or end panels with
• disconnectable busbar voltage transformer
• disconnectable busbar connection
• make-proof earthing switch at the busbar
• top-mounted busbar sectionalizer
Installation
gas while mounting the fixing
6
139/214