Removal Of Voltage Transformers Type 4Mt7 From The Cable Feeder - Siemens 8DA10 Series Installation And Operating Instructions Manual

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
25.3

Removal of voltage transformers type 4MT7 from the cable feeder

Fig. 141: 4MT7 voltage transformer
➭ Isolate and earth the cable feeder.
➭ Verify safe isolation from supply.
➭ Remove the voltage transformer. To do this, remove the 4 bolts of the fixing brackets at the
panel connection cover. Bolt size M10
Fig. 142: Removing the voltage transformer
Installation
Panel connection housing
Inside-cone bushing for primary
terminal of transformer
Primary terminal at the voltage
transformer
Silicone adapter
Fixing bracket (fixed at the voltage
transformer housing)
4MT7 voltage transformer
Low-voltage plug connection
Inside-cone bushing for cable
Panel connection cover