Constructional stipulations

18.1

Switchgear room

The switchgear can be used at the following locations as an indoor installation according to
IEC 61936 (Power Installations exceeding AC 1 kV) and VDE 0101:
• Lockable electrical service locations. Requirements on lockable electrical service locations
(room or location):
- Are exclusively used for operation of electrical equipment.
- Are kept under lock and key.
- Access is exclusively restricted to electricians and persons who have been properly
instructed in electrical engineering.
- Untrained or unskilled persons may only enter under the supervision of electricians or
persons who have been properly instructed in electrical engineering.
• Outside lockable electrical service locations at places which are not accessible to the public.
Enclosures of switchgear can only be removed with tools.
Observe the following points when preparing the switchgear room:
• Base frame and switchgear dimensions
• Transport ways to the switchgear room
• Distribution and intermediate storage spaces
• Size of the room and the doors
• Construction and load-bearing capacity of the floor
• Illumination, heating, power and water supply
• Dimensions of installation scaffoldings and foundation rails
• Installation of high-voltage cables
• Earthing system
• Switchgear room free of dirt and dust
Fig. 19:
Room planning
1
Room height
Lateral wall distance from the switchgear front
Floor opening for control cables
Floor opening for high-voltage cables
Lateral wall distance from the rear side of the switchgear in case of wall-
standing arrangement
Lateral wall distance in case of free-standing arrangement
1
If there are any busbar components, the room may have to be higher.
2
For large panel connection housings (versions 4 and 5), the dimension must not be smaller
than 1145 mm.
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
mm
≥ switchgear height + 200
≥ 800
210
1145
≥ 100
≥ 800