Operation
1
Initial situation
3
➭
Push the interrogation lever downwards.
5
➭
Switch the left-hand three-position disconnector to OPEN position
(insert the operating lever for the DISCONNECTING function and turn
180° counter-clockwise).
166/214
Decoupling busbar sections
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Open the circuit-breaker.
4
➭
Push the left-hand control gate to the left.
6
➭
Remove the operating lever for the DISCONNECTING function.
The interrogation lever and the left-hand control gate return to their initial