Installation
Mounting
protection plates
(if not pre-assembled
at the factory)
136/214
30

Installation of degree of protection version IPX1

Degree of protection version IPX1 for panels with and without busbar earthing switch
Fig. 158: Basic scheme with 850 mm low-voltage compartment
Protection plate for left end panel
Sealing ledge for intermediate panels
Protection plate for intermediate panels
Left-hand angle
30.1

IP31D - protection against vertically falling water drops

➭ Stick sealing straps ③ on the roof plates of panels without busbar earthing switch.
➭ Mount protection plate for intermediate and end panels. To do this, use bolts M6x25.
Tightening torque: 12 Nm.
Fig. 159: Example: Fastening protection plate for end panel and intermediate
panel (basic scheme)
Protection plate for left end panels (6 bolts M6x25)
Protection plate for intermediate panels (6 bolts M6x25)
Sealing strap
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
Protection plate for busbar earthing switch
Right-hand angle
Protection plate for right end panels located beside
busbar earthing switches
Felt strips between the individual panels, and felt
strips between roof plate and protection plate