Installing The Earthing Busbar - Siemens 8DA10 Series Installation And Operating Instructions Manual

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Earthing busbars at the
intermediate panel
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
21.6

Installing the earthing busbar

Earthing busbars at the switchgear
The earthing busbar runs at the rear of the switchgear frames. The units of the earthing
busbars overlap. The earthing busbars are interconnected with two bolts M12 and
a tightening torque of 70 Nm each.
➭ Remove the bolts ② at the joint.
➭ Remove the upright earthing busbar ① .
➭ Put the upright earthing busbar with the bolted joint aside for later reuse.
Fig. 73:
As-delivered condition of panel
to be lined up
➭ Push the removed earthing busbar horizontally into the switchgear frame so that it will
overlap with the earthing busbar of the next panel.
➭ At the joint, bolt the earthing busbars of the adjacent panels together using 2x bolts M12
including contact washers, conical spring washers and nuts. To do this, reuse the
disassembled bolted joint. Tightening torque: 70 Nm.
Fig. 74:
Interconnecting the earthing busbars
Short-circuit bridge at the circuit-breaker housings
2x M12 with contact washers, conical spring washers and nuts (top view onto the joint)
Earthing busbar connection to the next panel
Earthing busbar connection of adjacent panels
Short-circuit bridge at the panel connection housings
➭ Repeat the assembly operations for all panels until all earthing busbars have been
interconnected.
Upright earthing busbar
2x M12 with contact washers,
conical spring washers and nuts
(top view onto the joint)
Switchgear frame
Short-circuit bridge at
the circuit-breaker housings