Operation
160/214
Disconnecting the feeder from the busbar
1
Initial situation
3
➭
Push the interrogation lever downwards.
5
➭
Switch the three-position disconnector to OPEN
position (insert the operating lever for the
DISCONNECTING function and turn 180° counter-
clockwise).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
➭
Open the circuit-breaker.
4
➭
Push the control gate to the left.
6
➭
Remove the operating lever for the
DISCONNECTING function.
The interrogation lever and the control gate return to
their initial position.