Operation
160/214
Disconnecting the feeder from the busbar
1
Initial situation
3
Push the interrogation lever downwards.
5
Switch the three-position disconnector to OPEN
position (insert the operating lever for the
DISCONNECTING function and turn 180° counter-
clockwise).
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
2
Open the circuit-breaker.
4
Push the control gate to the left.
6
Remove the operating lever for the
DISCONNECTING function.
The interrogation lever and the control gate return to
their initial position.