Siemens 8DA10 Series Installation And Operating Instructions Manual page 63

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Preparing
busbar assembly on
the right end panel
Re-assembling the
busbars
861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
This operation is only performed if there is a horizontal flange cover available on the busbar
housing of the right end panel.
➭ Remove all flange covers ② from the assembly openings of the short busbar housing ① .
➭ If required, remove the protective caps from the bolts at the busbar ends, and loosen the
bolts.
Fig. 42:
Short busbar housing in right end panel
of fixed-mounted switchgear assembly
This operation is only performed if one of the following components is mounted on the
busbar housings of the panel to be lined up.
In these cases, the busbar joints are not accessible anymore after the panels have been
interconnected.
- Disconnectable busbar connection
- Disconnectable busbar voltage transformer
- Make-proof busbar earthing switch
- top-mounted busbar sectionalizer
Before starting to interconnect the panels, the busbar sections of the fixed-mounted panel
must be re-assembled to the panel to be lined up. The illustrations below show the state after
re-assembling.
Fig. 43:
Busbar re-assembled (example 1250 A)
Short busbar housing of the fixed-mounted
panel
Assembly openings (horizontal flanges)
Joint of the fixed-mounted panel
Vertical flanges of the fixed-mounted panel
Busbar
Short busbar housing
Flange cover
4 bolts with protective caps at the joint of
the busbar ends
NOTICE
Transformer connection housing for the
contact of the busbar voltage transformer
Busbar housing of the panel to be lined up
Joint of the panel to be lined up
Vertical flanges of the panel to be lined up
Busbar support
Installation
63/214