Checking The Sf6 Gas Pressure - Siemens 8DA10 Series Installation And Operating Instructions Manual

Medium-voltage switchgear
Hide thumbs Also See for 8DA10 Series:
Table of Contents

Advertisement

Installation
60/214
20.7
Checking the SF
To exclude any gas losses caused by transportation in the gas compartments filled at
the factory, the indications of the gas pressure manometers at the panels must be checked.
Insufficient gas filling can cause injury or property damage.
Operating the switchgear without service readiness due to insufficient gas filling can
cause injury and the destruction of parts of the switchgear.
➭ Before performing any switching operation, check the gas pressure in the compartments
pre-filled at the factory on the associated gas pressure indicators. The values must not drop
below the temperature-dependent limit values.
➭ Do not install, commission or operate a switchgear with incorrect or too low SF
pressures. If required, isolate the switchgear and put it out of service.
➭ Inform the competent regional Siemens representative.
Fig. 37:
Gas pressure manometers at the panel
Fig. 38:
Indication of gas pressure manometer
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
gas pressure
6
CAUTION
Gas pressure manometers for
the busbar compartments
Gas pressure manometers for
the circuit-breaker /
panel connection housings
Signaling contact: Pressure lower
than minimum functional level
Signaling contact:
Minimum functional level 100 kPa
Gas pressure indicator:
Rated functional level 120 kPa
Signaling contact:
Maximum functional level 180 kPa
The data in kPa are values at 20 °C
ambient air temperature
gas
6