Removal Of Voltage Transformers Type 4Mt7 From The Cable Feeder - Siemens 8DB10 Installation And Operating Instructions Manual

Extendable fixed-mounted circuit-breaker switchgear up to 40.5 kv
Table of Contents

Advertisement

864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
27.3

Removal of voltage transformers type 4MT7 from the cable feeder

Fig. 119: 4MT7 voltage transformer
➭ Isolate and earth the cable feeder.
➭ Verify safe isolation from supply.
➭ Remove the voltage transformer. To do this, remove the 4 bolts of the fixing brackets at
the panel connection cover, bolt size M10.
Fig. 120: Removing the voltage transformer
ATTENTION
Risk of injury! While being removed from the bushing, the voltage transformer can detach
suddenly.
➭ Remove the voltage transformer uniformly downwards.
➭ Do not use excessive force.
Installation
Panel connection housing
Inside-cone bushing for primary
terminal of transformer
Primary terminal at the voltage
transformer
Silicone adapter
Fixing bracket (fixed at the voltage
transformer housing)
4MT7 voltage transformer
Low-voltage plug connection
Inside-cone bushing for cable
Panel connection cover
111/214