Powering On the Appliance

This section contains power-on procedures for Oracle ZFS Storage Appliance disk shelves and
storage controllers.
Caution -
described in
Follow these steps to power on the appliance:
1. Power on disk shelves using the appropriate procedure:
2. Power on controllers. See
Use the following procedures to power off the appliance:
"Powering Off a Controller" on page 234
"Powering Off a Disk Shelf" on page 235

Powering On a DE3-24 or DE2-24 Disk Shelf

Use the following procedure to power on a DE3-24P, DE3-24C, DE2-24P or DE2-24C disk
shelf.
Ensure you have met the following electrical safety measures before applying power to the disk
Before You Begin
shelf:
Provide a suitable power source with electrical overload protection to meet the power
supply input voltage range of 100-240 VAC, 50-60 Hz. The disk shelves are compatible
with 100-120 VAC or 200-240 VAC sources. The power source must not be overloaded by
the total number of disk shelves in the cabinet. At full load, each DE3-24 or DE2-24 draws
707.8W.
The power source must provide a reliable earth connection for each disk shelf and the
cabinet.
Do not power on disk shelves and controllers until all other cabling is complete, as
"Cabling the Appliance" on page
"Powering On a DE3-24 or DE2-24 Disk Shelf" on page 231
"Powering On a Sun Disk Shelf" on page 233
"Powering On a Controller" on page
219.
233.
Powering On the Appliance