Appendix B Programmer-Defined Settings - Kohler Decision-Maker 3000 Operation

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

Use the table below to record programmer-defined
settings during the generator set controller setup and
calibration. The controller default settings and ranges
provide guidelines. The table contains all faults with
ranges and time delays including items that do not have
adjustments. Some notices give the programmer a
choice to make them active
programmer-defined settings result when the controller
logic does not allow changes or the values are engine
limited.
Programmer-Defined Settings
Description
Engine Functions
Critically high fuel level
(diesel-powered models only) *
ECM communications loss
ECM diagnostics (multiple
inputs) [
ECM diagnostics (multiple
inputs) [
ECM faults (address conflict)
ECM faults (model mismatch)
Engine over speed
Engine start aid active
Engine under speed
Fuel tank leak *
Fuel tank leak *
High battery voltage
High coolant temperature
High coolant temperature
High fuel level (diesel-powered
models only) *
Low battery voltage
Low coolant level *
Low coolant temperature
Low cranking voltage
Low engine oil level *
Low engine oil level *
Low fuel level (diesel models) *
Low fuel level (diesel models) *
TP-6694 7/11

Appendix B Programmer-Defined Settings

Not adjustable
Write
Access
Controller Display
Display
Message
SiteTech
Fuel Level Critically
High
ECM Comm Err
Shutdwn
ECM xxxxxx Warning
ECM xxxxxx Shutdwn
ECM Addr Err
Shutdwn
ECM Mismatch
Shutdwn
Eng Speed High
S
Shutdwn
Starting Aid Notice
Eng Speed Low
S
Shutdwn
Fuel Leak Warning
Fuel Leak Shutdwn
Battery High Warning
S
Coolnt Temp High
Warning
Coolnt Temp High
Shutdwn
Fuel Level High
Warning
Battery Low Warning
S
Coolant Lvl Low
Shutdwn
Coolant Temp Low
Warning
Lo Crank Vlt Warning
Oil Level Low Warning
Oil Level Low Shutdwn
Fuel Level Low
Warning
Fuel Level Low
Shutdwn
SiteTecht setup software is required for programming
the Decision-Makerr 3000 controller. Contact your local
distributor/dealer for assistance.
Note: Inhibit time delay is the time delay period after
crank disconnect.
Note: The engine ECM may limit the crank cycle even if
the controller is set to a longer time period.
GenSet
Mode
Always
Range
Default
Running
Setting
Selection
Stopped
0--100%
95%
0--255
0
A
105--120%
115%
A
75--95%
85%
A
110--135%
125%
0--100%
90%
A
80--105%
100%
16_C
Fixed
(60_F)
Fixed
60%
0--100%
35%
0--100%
5%
Time
Default
Delay
Time
Programmer-
Range
Delay
Defined
Settings
(sec.)
(sec.)
0--10
5
Fixed
10
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Not adjustable
Fixed
10
Not adjustable
0--10
0
(0--30
(0
inhibit)
inhibit)
0--10
0
(0--30
(0
inhibit)
inhibit)
0--10
5
Fixed
90
Not adjustable
Fixed
5
Not adjustable
0--10
5
(0--30
(0
inhibit)
inhibit)
Fixed
6
Not adjustable
Not adjustable
Not adjustable
0--10
10
0--10
0
Appendix 87