6.1.7

Remote Emergency Stop Kit

The emergency stop kit allows immediate shutdown of
the generator set from a remote location.
Figure 6-14 and Figure 6-15. If the emergency stop
switch activates, the EMERGENCY STOP lamp lights
and the unit shuts down. Before attempting to restart the
generator set, reset the emergency stop switch (by
replacing the glass piece) and reset the generator set by
pressing the master control switch OFF/RESET button.
Use the single glass piece located inside the switch for
replacement and order additional glass pieces as
service parts.
See Section 2.3.3, Emergency Stop
Switch Resetting.
See Section 6.2, Accessory Connections, for terminal
identifications.
Figure 6-14 Emergency Stop Kit
GM67191-B
Figure 6-15 Remote Emergency Stop Kit
Connections
TP-6694 7/11
6.1.8

Remote Reset Feature

The remote reset switch provides generator set
See
controller resetting after a fault shutdown at a remote
location.
user-supplied switch connection.
Press and hold the switch for 2--3 seconds and release
to reset the generator set controller.
See Section 6.2, Accessory Connections, for terminal
identifications.
REMOTE RESET SWITCH
CONTACTS NORMALLY OPEN
MOMENTARY CLOSED TO
ACTIVATE
Figure 6-16 Remote Reset Switch Connections
Switch Rating
Gauge
18--20
14
A-222654
10
TP-5352-1
Figure 6-17 Switch Rating and Wiring
See Figure 6-16 and Figure 6-17 for
CONNECT TO TB1
as a Digital Input
12 volts DC minimum, 1 amp minimum
Wiring Recommendation
m (ft.)
30.5 (100)
153 (500)
305 (1000)
Recommendations
Section 6 Accessories
GM16088A-A-/TP--6694