Genset Calibration - Kohler Decision-Maker 3000 Operation

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

2.6.8

GenSet Calibration

This menu is only available in controller firmware
versions before 3.0.25.
Menu—Reset Calibration with controller firmware
version 3.0.25 or higher.
Display provides access to the calibration factors for
metering (volts and amps).
voltage or replacing the main logic control circuit board
requires calibration adjustment. Connect a meter with a
minimum accuracy of 1% to the generator set output
leads to calibrate the voltage-sensing logic.
GenSet Calibration
GenSet ---->
Calibration
User Selectable - ->
TP-6694 7/11
Go to Generator Metering
Changing the system
Enter calib?
No
OR
Enter calib?
Yes
Volts L1--L2:
#.# V
Volts L2--L3:
#.# V
Volts L3--L1:
#.# V
Volts L1--N:
#.# V
Volts L2--N:
#.# V
Volts L3--N:
#.# V
Current L1:
#.# A
Current L2:
#.# A
Current L3:
#.# A
The user can individually calibrate the values or reset all
of them. The local display Reset all calib? No or Yes.
Select No to make no changes and exit GenSet
Calibration. Select Yes to reset all of the values.
When calibrating voltage, the metered value and the
number being entered as the calibrated value must be
within 10% of the system operating voltage.
When calibrating current, the metered value must be at
least 25% of the rated current on units smaller than
100 kW and at least 50 amps on units rated larger than
100 kW. The number being entered as the calibrated
value must within 10% of the metered value.
GenSet ---->
Calibration
Reset
calibration
Reset
calibration
Reset
calibration
<----Exit
Calibration
Reset all
calib? No
OR
Reset all
calib? Yes
Section 2 Operation
43