P25 Connector
RJ45 Remote I/O In
Connects to DEC 3000 P23
P26 Connector
RJ45 Remote I/O Out
Open
P27 Connector
CAN Terminator
Place the P27 jumper on the IN pins
P28 Connector
Single-Ended (0- -5 V) Analog Input Connections
Terminal
Description
P28--GND
AGND Analog Return
P28--VN1
NO Connection
P28--VP1
ACH1 Signal
P28--+5V
Supply (.05 amp max.)
P28--GND
AGND Analog Return
P28--VN2
NO Connection
P28--VP2
ACH2 Signal
P28--+5V
Supply (0.05 amp max.)
P28 Connector
Differential (+/- -3 V) Analog Input Connections
Terminal
Description
P28--GND
AGND Analog Reference
P28--VN1
ACH1 Negative Differential Signal
P28--VP1
ACH1 Positive Differential Signal
P28--+5V
Supply (.05 amp max.)
P28--GND
AGND Analog Reference
P28--VN2
ACH2 Negative Differential Signal
P28--VP2
ACH2 Positive Differential Signal
P28--+5V
Supply (0.05 amp max.)
P29 Connector
2 Amp. K1 Relay Output (2.1) Connections
Terminal
Description
P29--NC
Normally Closed
P29--COM Common
P29--NO
Normally Open
Figure 6-27 Input/Output Module Board Connections
TP-6694 7/11
P30 Connector
2 Amp. K2 Relay Output (2.2) Connections
Terminal
Description
P30--NC
Normally Closed
P30--COM Common
P30--NO
Normally Open
P31 Connector
2 Amp. K3 Relay Output (2.3) Connections
Terminal
Description
P31--NC
Normally Closed
P31--COM Common
P31--NO
Normally Open
P32 Connector
10 Amp. K4 Relay Output (2.4) Connections
Terminal
Description
P32--NC
Normally Closed
P32--COM Common
P32--NO
Normally Open
10 Amp. K5 Relay Output (2.5) Connections
Terminal
Description
P32--NC
Normally Closed
P32--COM Common
P32--NO
Normally Open
P28 Connector Designations
Terminals
Controller
on Board
Designation
P28--GND
P28--VN1
DIn B1
P28--VP1
P28--+5V
P28--GND
P28--VN2
Din B2
P28--VP2
P28--+5V
SiteTech
Designation
B1
B2