Kohler Decision-Maker 3000 Operation page 15

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

Fuel Level % displays the fuel tank level for diesel-
powered models. This value also shows in the Overview
Menu.
Battery displays the DC voltage of the engine starting
battery(ies). This value also shows in the Overview
Menu.
Fuel Pressure displays the fuel line pressure at the
generator set inlet for gas-powered models. This value
also shows in the Overview Menu.
Generator Metering Menu
Total Power kVA and kW displays alternator output as
actual output values.
Rated Power displays alternator output as a
percentage of the entered data value.
Volts displays the alternator output AC voltages. The
display shows all line-to-line and line-to-neutral voltage
combinations
for
three-phase
configurations.
Current displays the alternator output AC amps. The
display shows each line (L1-L2-L3) of three-phase
models or L1-L2 current for single-phase models.
Frequency (Hz) value displays for the output AC
voltage. This value also shows in the Overview Menu.
Reset Calibration providing the means to reset the
configuration values is available in this menu in
controller firmware version 3.0.25 or higher.
The calibration values are reviewable at all times and
provide the calibration of the voltage and current
sensing logic. Changing the system voltage or replacing
the circuit board requires a calibration adjustment.
To enable calibration, start the generator set and select
the Volts L1-L2 display.
pushbutton/rotary selector dial until the Calibration
Enabled popup appears. Calibration of each display is
now available.
The display will show the following
values for three-phase generator sets. Single-phase
generator sets will only display items marked (*).
D
Volts L1-L2 *
D
Volts L2-L3
D
Volts L3-L1
D
Volts L1-N *
D
Volts L2-N *
D
Volts L3-N
D
Current L1 *
D
Current L2 *
D
Current L3
TP-6694 7/11
or
single-phase
Then push and hold the
The user can change individual values or can select
Reset Calib?- -Yes to reset all values. The Reset Calib?
display will only show if calibration is enabled. Refer to
the requirements shown with Generator Set Calibration
in 2.3.7 Status and Notice Digital Displays.
To disable calibration, Rotate the pushbutton/rotary
selector dial until the <- -Return popup appears.
Momentarily press the pushbutton/rotary selector dial.
Stop the generator set if not already done.
Generator Set Information Menu
GenSet M/N displays the generator set model number.
GenSet S/N displays the generator set serial number.
Controller S/N displays the controller serial number.
Generator Set Run Time Menu
Engine Run Time displays the total run time hours.
This value also shows in the Overview Menu.
Engine Loaded displays the total loaded hours.
Engine Starts displays the total number of generator
set startup events.
Total Energy displays the total kW hours.
Generator Set System Menu
The values in this menus are user-entered for the
generator set configuration and are NOT measured
values of the generator set.
Changes to the Generator Set System menu require the
use of SiteTecht software except for Measure System
and Contrast selections.
System Frequency displays the programmer-entered
L1-L2-L3 output voltage frequency for three-phase or
the L1-L2 output voltage frequency for single-phase.
System Phase displays the programmer-entered
configuration as Single Phase, Single Phase Dog Leg,
Three Phase Wye, or Three Phase Delta.
System Voltage displays the programmer-entered
L1-L2-L3 output voltage for three-phase or the L1-L2
output voltage for single-phase.
Power Rating displays the programmer entered kW
value for the generator set.
Amp Rating displays the programmer entered current
value for the generator set.
Power Type displays the programmer entered
generator set application configuration as Standby or
Prime.
Section 1 Specifications and Features
15