All analog input selection and setup adjustments are
done using SiteTecht software. The following terms
and descriptions are part of the setup procedure.
D
Enabled. This menu indicates whether or not the
input is enabled. If the input is not enabled, the
controller will ignore this input signal.
D
Inhibit Time Delay. The inhibit time delay is the time
period following crank disconnect during which the
generator set stabilizes and the controller does not
detect the fault or status event. The controller will
ignore the input until the inhibit time expires. If the
inhibit time is set to zero, the input is monitored at all
times, even when the generator is not running. The
inhibit time delay range is from 0 to 60 seconds.
D
Time Delay (shutdown or warning). The time delay
follows the inhibit time delay. The time delay is the
time period between when the controller first detects
the fault or status event and the controller warning or
shutdown lamp illuminates. The delay prevents any
nuisance alarms. The time delay range is from 0 to
60 seconds.
Analog Inputs
Analog ---->
Inputs

2.6.13 Event Log

Displays up to 1000 stored status, warning, and
shutdown events. After the first 1000 events, each
additional new event replaces the oldest event. See
1.2.4 Controller Fault Diagnostics for a list of possible
events.
Event Log
Event Log ---->
48
Section 2 Operation
AIn A1
#####
AIn B1
#####
AIn B2
#####
#####
(Message Text)
(Scroll through up to 1000
max. stored events)

2.6.14 Volt Select

This menu is only available in controller firmware
version 2.8.22 and higher.
This menu allows the user to readily change controller
voltage settings. The volt select feature is typically used
in towable or temporary applications.
Note: The volt select menu requires initial activation by
SiteTecht software.
select True to activate the volt select menu.
Note: The generator set output leads require voltage
reconnection if the generator set does not have a
voltage selector switch installed.
With the generator set stopped, go to the Volt Select
menu.
Then push and hold the pushbutton/rotary
selector dial until the voltage selection starts to flash.
Volt selection is now available. Scroll to the desired
voltage and momentarily press the pushbutton/rotary
selector dial to confirm the voltage selection.
Volt Select
Volt Select: ---->
###/### V # Ph
In SiteTecht software,
120/240 V 1 Ph
120/208 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
120/240 V 3 Ph
TP-6694 7/11