6.1.10 Run Relay Kit

The run relay kit energizes only when the generator set
runs. Use the run relay kit to control air intake and
radiator louvers, alarms, and/or other signalling
devices. See Figure 6-21 and Figure 6-22.
See Section 6.2, Accessory Connections, for terminal
identifications.
Figure 6-21 Run Relay Kit
Figure 6-22 Run Relay Connections
80
Section 6 Accessories

6.1.11 Shunt-Trip Line Circuit Breaker

A shunt-trip line circuit breaker provides a 12- or 24-DC
volt solenoid within the line circuit breaker case that can
energize the trip mechanism. This feature allows the
circuit breaker to be tripped by the common fault (32A).
Connection requires a shunt-trip wiring kit and a dry
contact kit. See Figure 6-23 and Figure 6-24.
The optional common fault relay shown in Figure 6-24
as DCB1 has contacts rated at 10 amps at 28 VDC or
120 VAC and is used to trigger the shunt-trip line circuit
breaker kit.
273705
Figure 6-23 Shunt-Trip Wiring (Standard)
GM67191-B
Figure 6-24 Shunt-Trip Relay Kit and Line Circuit
Breaker Wiring (Shown with Common
Fault/Failure Relay Kit)
GM67191-B
GM67191-B