Kohler Decision-Maker 3000 Operation page 35

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

Engine Start Aid Active.
indicates that the start aid is active and will energize an
engine equipped preheat or ether system during the
crank cycle. Use SiteTecht software to set up this
feature. The local display shows Starting Aid Notice.
Engine Start Delay Active.
indicates that the delay for engine start is active where
the generator set will not start right after the RUN button
is pressed. The unit will start cranking after the time
delay times out. The local display shows Start Delay
Notice.
Engine Started.
This status indicates that the
generator set start circuit is closed allowing the engine to
crank and run. The local display shows Engine Start
Status.
Engine Stopped.
This status indicates that the
generator set start circuit is open causing the engine to
shut down. The local display shows Engine Stop Status.
Generator Running. This notice indicates that the
generator set has started and is running. The local
display shows Gen Running Notice.
Generator Set Calibration (User Defined).
selectable display is in the GenSet Calibration Menu
allowing the user to calibrate the controller and
generator set. Use the Pushbutton/Rotary Selector Dial
to navigate and select this feature.
Changes to this display must be done with the generator
set running. The local display shows Enter calib? No or
Yes. Select No to make no change. Select Yes to
calibrate the following values:
D
Volts L1--L2: x.x V
D
Volts L2--L3: x.x V
D
Volts L3--L1: x.x V
D
Volts L1--N: x.x V
D
Volts L2--N: x.x V
D
Volts L3--N: x.x V
D
Current L1: x.x A
D
Current L2: x.x A
D
Current L3: x.x A
The user can individually calibrate the values above or
reset all of them. The local display Reset all calib? No or
Yes. Select No to make no changes and exit GenSet
Calibration. Select Yes to reset all of the values.
When calibrating voltage, the metered value and the
number being entered as the calibrated value must be
within 10% of the system operating voltage.
TP-6694 7/11
This notice message
This notice message
This
When calibrating current, the metered value must be at
least 25% of the rated current on units smaller than
100 kW and at least 50 amps on units rated larger than
100 kW. The number being entered as the calibrated
value must be within 10% of the metered value.
Measurement Units (User Defined). This selectable
display is in the GenSet System Menu allowing the user
to choose between Metric and English displays. Use the
Pushbutton/Rotary Selector Dial to navigate and select
this feature. Changes to this display can be done with
the generator set running or stopped. The local display
shows Meas Units: Metric or Meas Units: English.
NFPA 110 Alarm Active.
indicates that the alarm for NFPA 110 is active. The fault
lamp illuminates yellow (warning) or red (shutdown), the
alarm horn sounds, and the units shuts down (if a
shutdown fault is detected) when the NFPA 110 fault
signals the controller. The local display shows the
respective fault message. The NFPA 110 faults include:
D
Battery charger fault
D
EPS supplying load
D
High battery voltage
D
High coolant temperature shutdown
D
High coolant temperature warning
D
High engine speed
D
Low battery voltage
D
Low coolant level
D
Low coolant temperature warning
D
Low fuel (level or pressure)
D
Low oil pressure shutdown
D
Low oil pressure warning
D
Master switch not in auto
D
Overcrank
Remote Start. This status indicates that the generator
set start circuit was closed from a remote location
allowing the engine to crank and run. The remote
location is typically a set of contacts on a transfer switch
or remote start switch. The local display shows Remote
Start Status.
System Ready. This status indicates that the generator
set is in the AUTO mode and available to start if the start
circuit is closed.
The local display shows System
Ready.
System Timer Failed. This notice indicates that the
controller timer logic has failed to time out a designated
function. The local display shows Timer Error Notice.
This notice message
Section 2 Operation
35