Voltage Reconnection Procedure (Software Version 2.8 Or Higher); Voltage Reconnection Procedure (Software Version Before 2.8) - Kohler Decision-Maker 3000 Operation

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

5.2 Voltage Reconnection
Procedure
(Software version 2.8 or higher)
1. Press
the
generator
OFF/RESET button.
2. Turn the controller pushbutton/rotary selector dial
until it stops at the Volt Select menu.
Figure 5-1.
Note: If the Volt Select menu does not appear, the
controller voltage selection feature was not
activated using SiteTecht software.
Volt Select:
---->
###/### V # Ph
TP-6694-2
Figure 5-1 Volt Select Menu
3. Press the selector dial and the voltage selection
option (second line on the display) will start to flash.
4. Turn
the
selector
counterclockwise
selection option appears.
5. Press the selector dial. The second line on the
display will stop flashing and the new voltage will
appear.
6. Rotate the generator set voltage selector switch (if
equipped) to match the desired voltage shown on
the controller display. Skip steps 7--9 and go to
step 10.
If the generator set does not have a voltage
selection switch, continue to step 7
7. Disconnect the generator set engine starting
battery, negative (--) lead first. Disconnect power to
the battery charger (if equipped).
68
Section 5 Voltage Reconnection
set
master
control
120/240 V 1 Ph
120/208 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
120/240 V 3 Ph
dial
clockwise
until
the
desired
voltage
8. Use Figure 5-2, Figure 5-3, or Figure 5-4 to
determine the generator set voltage configuration.
Note the original voltage and reconnect as needed.
Route leads through current transformers (CTs)
and connect them according to the diagram for the
desired phase and voltage.
Note: Position current transformers CT1, CT2,
and CT3 with the dot or HI side CT marking
See
toward the generator set.
9. Reconnect the battery, negative lead last.
10. Press the generator set master control RUN button
to start the generator set. Check the digital display
for correct voltages using 2.6.4 Generator
Metering.
11. Press
the
OFF/RESET button to stop the generator set after
completing the voltage adjustments.
5.3 Voltage Reconnection
Procedure
(Software version before 2.8)
1. Press
the
OFF/RESET button.
2. Disconnect the generator set engine starting
battery, negative (--) lead first. Disconnect power to
the battery charger (if equipped).
3. Use Figure 5-2, Figure 5-3, or Figure 5-4 to
determine the generator set voltage configuration.
Note the original voltage and reconnect as needed.
Route leads through current transformers (CTs)
or
and connect them according to the diagram for the
desired phase and voltage.
Note: Position current transformers CT1, CT2,
and CT3 with the dot or HI side CT marking
toward the generator set.
4. Reconnect the battery, negative lead last.
5. Use SiteTecht software to update the information.
6. Refer to 2.6.8 for generator set calibration at the
controller.
7. Press the generator set master control RUN button
to start the generator set. Check the digital display
for correct voltages using 2.6.4 Generator
Metering.
8. Press
the
OFF/RESET button to stop the generator set after
completing the voltage adjustments.
generator
set
master
generator
set
master
generator
set
master
TP-6694 7/11
control
control
control