Controller Resetting (Following System Shutdown Or Warning); Menu Displays - Kohler Decision-Maker 3000 Operation

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

Voltage Regulator Adjustment (User Defined). This
feature is in the Voltage Regulator Menu allowing the
user to fine adjust the output voltage.
Pushbutton/Rotary Selector Dial to navigate and select
this feature. Changes to this display must be done with
the generator set running. The local display shows
Enter volt reg? No or Yes. Select No to exit the voltage
regulator menu. Select Yes to change the local display
VR Volt Adj: xxx.x V.
2.3.8
Controller Resetting (Following
System Shutdown or Warning)
Use the following procedure to restart the generator set
after a system shutdown or to clear a warning lamp
condition. This procedure includes the resetting of the
optional remote annunciator.
Refer to Section 2.3.3, Emergency Stop Switch Reset
Procedure, to reset the generator set after an
emergency stop.
1. Disconnect the generator set load using the line
circuit breaker or automatic transfer switch.
2. Correct the cause of the fault shutdown or warning.
See the Safety Precautions and Instructions
section of this manual before proceeding.
3. Start the generator set by pressing the generator
set master control OFF/RESET button and then
press the RUN button.
When equipped, the remote annunciator alarm
horn sounds. Press the ALARM SILENCE/LAMP
TEST button to stop the alarm horn. The lamp
turns off.
36
Section 2 Operation
4. Test operate the generator set to verify correction
of the shutdown cause.
Use the
5. Press
OFF/RESET button to stop the generator set.
6. Press the generator set master control AUTO
button.
7. Silence the controller alarm horn by pressing the
ALARM SILENCE button.
8. Reconnect the generator set load via the line circuit
breaker or automatic transfer switch.
9. When equipped, the remote annunciator alarm
horn sounds. Press the ALARM SILENCE/LAMP
TEST button to stop the alarm horn. The lamp
turns off.

2.4 Menu Displays

Use the Menu Summary List section after reading and
understanding the features of the pushbutton/rotary
selector dial. See Section 1.2.3, Digital Display.
The Menu Summary List provides a quick reference to
the digital display data. Some digital display data may
not be identical to your display due to generator set
application differences.
represent main level data and the open bullet items are
sub-level data. The Menu Summary List indicates items
that are user selectable. Use SiteTecht software for
changing all other programmable information.
Section 2.6, Reviewing the Menu Displays, provides a
digital display menu overview and explains the
navigation using the pushbutton/rotary selector dial.
the
generator
set
The closed bullet items
master
control
TP-6694 7/11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents