Digital Inputs - Kohler Decision-Maker 3000 Operation

Industrial generator sets
Hide thumbs Also See for Decision-Maker 3000:
Table of Contents

Advertisement

2.6.10 Digital Inputs

Displays the selected programming user-defined digital
notice, warning, and shutdown inputs. These inputs
provide a multitude of choices for configuring
customized auxiliary inputs. See Figure 2-13 for a list of
digital input choices. For descriptions of the inputs listed
refer to the following:
D
2.3.5 System Fault Warning Lamp with Digital
Displays
D
2.3.6 System Fault Shutdown Lamp with Digital
Displays
D
2.3.7 Status and Notice Digital Displays
There is an optional 2 input/5 output (I/O) module board
available that can provide two additional digital (or
analog) inputs.
The displays for digital inputs appear as shown below
with Values true or false. Items shown in the display as
True are active.
D
DIn A1 (digital input A1) standard
D
DIn A2 (digital input A2) standard
D
DIn A3 (digital input A3) standard
D
DIn B1 (digital input B1) with I/O module board
D
DIn B2 (digital input B2) with I/O module board
All digital input selection and setup adjustments are done
using SiteTecht software. The following terms and
descriptions are part of the setup procedure.
D
Enabled. This menu indicates whether or not the
input is enabled. If the input is not enabled, the
controller will ignore this input signal.
Analog and
Digital Inputs
Auxiliary Input
Battery Charger Fault
Chicago Code Active
Engine Fuel Level
Fuel Tank Leak
Ground Fault
Low Engine Oil Level
Low Fuel Pressure
Figure 2-13 Analog and Digital Inputs
TP-6694 7/11
Low
Warning
Notice Warning
AD
AD
AD
AD
AD
AD
AD
AD
D
Inhibit Time Delay. The inhibit time delay is the time
period following crank disconnect during which the
generator set stabilizes and the controller does not
detect the fault or status event. The controller will
ignore the input until the inhibit time expires. If the
inhibit time is set to zero, the input is monitored at all
times, even when the generator is not running. The
inhibit time delay range is from 0 to 60 seconds.
D
Time Delay (shutdown or warning). The time delay
follows the inhibit time delay. The time delay is the
time period between when the controller first detects
the fault or status event and the controller warning or
shutdown lamp illuminates. The delay prevents any
nuisance alarms. The time delay range is from 0 to
60 seconds.
Digital Inputs
Digital ---->
Inputs
High
Critical High
Warning
Warning
D
D
DIn A1
#####
DIn A1
Value: True or False
DIn A2
#####
DIn A2
Value: True or False
DIn A3
#####
DIn A3
Value: True or False
Low
Shutdown
Shutdown
Shutdown
AD
D
D
D
Section 2 Operation
High
45