Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards.
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of
electrocution.
Short circuits.
Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Making line or auxiliary connections. Hazardous voltage
can cause severe injury or death. To prevent electrical
shock deenergize the normal power source before making any
line or auxiliary connections.
WARNING
Airborne particles.
Can
cause
blindness.
Wear protective goggles and clothing
when using power tools, hand tools,
or compressed air.
NOTICE
Electrostatic discharge damage. Electrostatic discharge
(ESD) damages electronic circuit boards.
electrostatic discharge damage by wearing an approved
grounding wrist strap when handling electronic circuit boards
or integrated circuits. An approved grounding wrist strap
provides a high resistance (about 1 megohm), not a direct
short, to ground.
TT-1443
9/07
Electrically ground the
Do not contact electrical
severe
injury
or
Prevent

1 Installation Procedure

Choose the annunciator location so that the total cable
length to connect all transfer switches in the ATS
network and the remote annunciator is no more than
1220 m (4000 ft.).
Note: The maximum cable length for RS-485 networks
is 1220 m (4000 ft.).
Be sure that the mounting structure can support the
weight of the annunciator assembly. The annunciator
weights are shown below.
Description
Assembly with NEMA 4 enclosure
Flush-mounted assembly with
mounting plate
Figure 3 Weights
1.1
Prepare the annunciator enclosure, if
used.
For annunciators installed in an enclosure, drill separate
holes in the top, bottom, or left side of the enclosure for
the power and signal cables. Remove burrs and metal
chips.
Use separate conduit for power and signal
connections.
Note: The enclosures provided with the kits meet
NEMA 4 requirements.
required to meet the desired NEMA rating (up to
NEMA 4) for the application.
Weight
4.2 kg (9 lb.)
1.4 kg (3 lb.)
Use conduit hubs as
3