Connecting Outputs - Eaton easy800 Manual

Control relay
Table of Contents

Advertisement

2 Installation

2.6 Connecting outputs

2.6 Connecting outputs
44
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Currents are measured in the 4 - 20 mA (0 - 20 mA) signal range. For current
measurement connect the output of the sensor to the current input (terminal
3 or 8), → section , "Temperature sensor", page 42.
When current measuring is activated, we recommend the
implementation of open-circuit monitoring via the diagnostics
contact R13. The expansion unit switches the diagnostics
contact to the 1 state if a current < 3 mA is present. Use current
sensors for the 4 - 20 mA signal range if you wish to evaluate
the diagnostics contact.
Temperatures are measured in the range -50 - +200 °C using PT100
temperature sensors. The sensor inputs 1 (terminal 4 - 6) and 2
(terminal 9 - 11) are used for temperature measuring.
On terminals 6 and 11, the analog expansion unit outputs a constant current
to the temperature sensor.
Connect the ground connection of a sensor to the corresponding 0 V input
(terminal 4 or 9) of the expansion unit.
You connect the temperature sensor directly to the relevant three terminals
of these sensor inputs. A three-wire connection or a two-wire connection is
possible.
With three-wire measuring, the line resistance is compensated by means of
a measuring bridge in the expansion unit.
With two-wire connections, connect a short-circuit bridge between terminals
5 and 6 or 10 and 11 (→ Figure 43, page 43).
The inputs and outputs of these analog expansion units require
the same reference potential (chassis ground) as the DC power
supply of the sensors and actuators.
Connect the 0 V of the DC power supply of the different
sensors with the 0 V of the DC power supply of the expansion
unit.
Devices either have transistor outputs or relay outputs. easy800 standard
outputs: The Q... outputs of both device versions are potentially isolated
from the power supply and the inputs and therefore potential-free.
EASY806-DC-SWD outputs: There is no potential isolation between the
outputs and
the local inputs
POW
SWD
Galvanic isolation is provided between AUX and NET.