Eaton easy800 Manual page 49

Control relay
Table of Contents

Advertisement

Q1
1
2
Figure 44:Connecting outputs, in this case Q1
The respective relay coils are actuated in the circuit diagram via the output
relays Q1...Q6 (Q8).
You can use the signal states of the output relays as N/O or N/C contacts in
the circuit diagram for additional switching conditions.
The relay or transistor outputs are used to switch loads such as fluorescent
tubes, filament bulbs, contactors, relays or motors. Prior to installation
observe the technical limit values and data for the outputs (→ Section
"Transistor outputs", Page 355).
See also:
"Connect relay outputs", Page 46.
"Connecting transistor outputs", Page 48.
"Connect analog output", Page 50.
The number of outputs of the easy800 standard can be increased by using an
expansion unit. The outputs of the EASY202-RE, EASY4..-DC-.E and EASY6..-
DC-. digital expansion units are detected by the easy800 standard
automatically - without any configuration.
The universal EASY4..-DC-ME expansion units allow you to process both
digital and analog values.
The factory activated analog outputs can also be processed
immediately, but should always be adapted to your application
during commissioning, → Section "Configuring the analog
expansion unit", Page 84.
All available input/output expansions → section 12.5, "Possible
combinations of basic devices and expansion units", page 362.
Whether an easy800 standard device has transistor or relay outputs can be
easily determined by the product designation. The easy800 standard devices
have an R in the key to part numbers for relay outputs and a T for transistor
outputs, e.g. EASY819-DC-RC and EASY821-DC-TC.
easy806-DC-SWD is provided with two transistor outputs Q1 and Q2 in order
to offer functions such as pulse width modulation and pulse output.
Parallel connection of outputs
The parallel connection of outputs Q1 and Q2 is not allowed on the
easy806-DC-SWD.
Up to four outputs can be connected in parallel on easy800 standard and the
expansion units in order to increase the power. This enables a maximum
output current of 2 A.
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Q1 q1
2 Installation
2.6 Connecting outputs