Eaton easy800 Manual page 209

Control relay
Table of Contents

Advertisement

HY01 A
+
>ON --.--.08
>OFF --.--.12
HY01 A
+
>ON --.04.--
>OFF --.10.--
HY01 A
+
>ON 02.--.--
>OFF 25.--.--
Example
Month/Day/Year: 11/11/07
Parameters
Function
On date
>ON
Off date
>OFF
Function of the function block
The year time switch can switch ranges, individual days, months, years or
combinations of all three.
Years
Switching at 00:00:
On on 01.01.2008 and
Off on 01.01.2013.
Months
Switching at 00:00:
On on 01 April every year.
Off on 01 November every year.
Days
Switching at 00:00:
On on the 2nd day of every month.
On on the 26th day of every month.
Entry rules
The contact switches (ON to OFF)
in the years.
in the defined months.
on the entered days.
CAUTION
The year time switch only operates correctly if you observe the
following rules:
The On year must be before the Off year,
ON and OFF times must be specified the same in pairs,
for example:
ON = Day/--/--, OFF = Day/--/--
ON = --/--/Year, OFF = --/--/Year,
ON = --/Month/Year, OFF = --/Month/Year
ON = Day/Month/Year, OFF = Day/Month/Year
Normally, the ON day should be before the OFF day;
otherwise, the exception described on Example 8
(→ section , "Example 8: Selecting a time range of two
days spanning the turn of the year (2-channel)", page 209)
on applies.
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com