Eaton easy800 Manual page 219

Control relay
Table of Contents

Advertisement

Inputs
I1: Assign the unscaled value to function block input I1.
X1 and Y1: You define the first support point of the straight line at function
block inputs X1 and Y1.
X2 and Y21: The second pair of values at function block inputs X2 and Y2
determines the second support point of the straight line.
You can assign the following operands to function block inputs I1, X1, Y1,
X2 and Y2:
Constant
Markers MD, MW, MB
Analog inputs IA01 to IA04:
IA01: Terminal I7
IA02: Terminal I8
IA03: Terminal I11
IA04: Terminal I12
Analog output QA01
Output
QV> of a different function block
...
Output
The output QV supplies the scaled value as an integer.
You can assign the following operands:
Markers MD, MW, MB
Analog output QA01
Function of the function block
The scaling function block must be enabled via coil LS..EN = 1
in order for it to work. If the coil LS..EN is not active, the entire
function block is deactivated and reset. The output value is set
to zero.
X1
Y1
Figure 153:Value scaling function block – reduce value range
a Source range
b Destination range
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
a
X2
b
Y2
5 Function blocks
5.20 LS, value scaling
215