Eaton easy800 Manual page 203

Control relay
Table of Contents

Advertisement

HW14
A
+
>DY1
>DY2
>ON
>OFF
Contacts and Coils
The contact of the function block is evaluated in the circuit diagram. It closes
for the on time and opens for the off time on the defined days.
Contacts
Meaning
Switching contact; closes in the defined period
HW..Q1
Example for a weekly timer:
HW14Q1---------------------------Ä Q 01
Figure 136:Wiring of the function block contact
The weekly timer controls a device output directly.
Parametric programming of the function block inputs/outputs
When using the function block in the circuit diagram for the first time, use
OK to automatically enter the general display of function block parameters,
as shown in the figure on the left. The function block settings are carried out
here. The display contains the following elements:
Function block: Weekly timer, number 14
HW14
Time switch channel: A
A
Parameter set can be called via the PARAMETERS menu
+
Day 1: Day on which the switch-on is to occur for the first time (start of time period).
>DY1
Day 2: Day on which the switch-off is to occur for the last time (end of time period).
>DY2
Closing delay: 00:00 - 23:59, No on switching: --:--
>ON
Break time: 00:00-23:59,
>OFF
No off switching: --:--
Channel
For each weekly timer channels A, B, C and D are available. These channels
all act jointly on the contact Q1 of the 7-day time switch.
Parameters
Function
Display of the parameters: Channel A
A
Display of the parameters: Channel B
B
Display of the parameters: Channel C
C
Display of the parameters: Channel D
D
Day 1 and day 2
These parameters DY1/DY2 are used to limit the period in which the output
HW..Q1 is switched.
Enter either a period of several days or only of one day:
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
5 Function blocks
5.16 HW, weekly timer