12 Appendix
12.3 Technical data
356
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Short-circuit protective device
Electronic
(evaluation possible via diagnostic input I16)
thermal
(evaluation possible via diagnostic input I15)
Short-circuit tripping current for R
(depending on number of active channels and
their load)
Maximum, total short-circuit current
Peak short-circuit current
in the event of short-circuit
on attempted restart of device after 10 s
Thermal cutout
Max. switching frequency of resistive load
Parallel wiring capability of outputs
with resistive load, with inductive load
with external suppressor circuit (see
section Connecting transistor outputs),
with combination within a group
Number of outputs (max.)
Max. total current
Caution!
Outputs must be actuated simultaneously
and for the same time duration.
Status display of the outputs
Inductive load without external suppressor circuit
General explanations: T
current is reached
L
≈ 3 T
T
= 3
0.95
0.65
R
easy800 standard:
Utilization categories in groups Q1 to Q4, Q5 to Q8
T
= 1 ms
Utilization factor per group g =
0.95
R = 48 Ω
Relative duty factor
L = 16 mH
Max. switching frequency
f = 0.5 Hz
Max. duty factor
DF = 50 %
10 mΩ
A
a
A
A
A
A
= time in milliseconds until 95 % of the stationary
0.95
EASY8..-DC-T..., easy800-SWD
easy800 standard: yes (Q1 – Q4)
easy800-SWD: yes (Q1/Q2)
easy800 standard: yes (Q5 – Q8)
easy800-SWD: no
easy800 standard: 0.7 I
2 per output
e
easy800-SWD: 0.15 to 0.35 per output
easy800 standard: 8
easy800 standard:16
easy800-SWD: 10A/80 ms
easy800-SWD: 10A/20ms
easy800 standard: yes
easy800-SWD: no
depending on cycle time
easy800 standard: yes
easy800-SWD: no
Group 1: Q1 to Q4
Group 2: Q5 - Q8
4
2
easy800 standard: LCD display
(if provided)
easy800-SWD: LED
0.25
%
100
Switching
1500
operations/h