5 Function blocks
5.4 BT, Data block Transformer
150
Control Relay easy800 11/11 MN04902001Z-EN www.eaton.com
Function block: Data block transfer, number 07
BT07
Operating mode: INI
INI
Parameter set can be called via the PARAMETERS menu
+
Start of source range or initialization markers (MB,MW,MD)
>I1
Destination range start
>I2
Number of elements to be written in bytes per range, number: 1 - 383
>NO
Operating mode
The operating mode setting defines whether marker ranges are to be copied
or initialized.
Parameters
Function
Initialize marker ranges
INI
Copy marker ranges
CPY
The factory setting of this parameter is INI.
Inputs
I1 and I2: Function block inputs I1 and I2 are used to define the beginning of
the source and destination range.
The entry at function block input NO determines the number of elements to
be written.
You can assign the following operands to function block inputs I1 and I2 and
NO:
Constant.
Markers MD, MW, MB.
Analog inputs IA01 to IA04:
IA01: Terminal I7.
IA02: Terminal I8.
IA03: Terminal I11.
IA04: Terminal I12.
Analog output QA01.
Output
QV of a different function block.
...
Specifying the marker range
Marker ranges can be specified with or without an offset.
Marker range without offset
If MB, MW or MD markers are specified at both I1 and I2 the number of the
markers is the start of comparison range.
Marker range with offset
If you wish to work with an offset, specify one of the following variables at
function block input I1 or I2.
Analog input IA..
Analog output QA..