General Emc Guidelines For Compliance - Toshiba W7 DN-57442-006 Installation & Operation Manual

Adjustable speed drives
Table of Contents

Advertisement

TIC has applied the following standards for systems
deployed in the European market:
Category
Emission
Electrostatic Discharge
Immunity
Electrical Fast Transient Burst
General EMC Guidelines for
Compliance
• Input EMI filters to reduce transmission and
radiation noise
(Table 3
• Use shielded power and control cables.
• Minimize cable lengths and DO NOT route
them parallel or bind them together.
ASD Model
Schaffner Filter
4220
FN 258-30-07
4270
FN 258-42-07
4330
FN 258-55-07
4400
FN 258-75-34
4500
4600
FN 258-100-35
4750
FN 258-130-35
410K
FN 258-180-40
412K
FN 258-250-40
415K
https://www.toshiba.com/tic/
W7B ASD Installation & Operation Manual
Table 2. EMC Standards.
Subcategory
Radiated
Conducted
Generic Industrial
Radiated
Lighting Surge
Conducted
Voltage Dip
and
Table
4).
Table 3. W7B ASD 460-Volt Filter Recommendations.
FLA @ 40° C
30
42
55
75
75
110
143
197
275
Safety Information and Precautions
Product Standards
Test Standard and Level
EN55011 Class A Group 1
EN55011 Class A Group 1
EN61800-3
• Earth the steel cabinet containing the ASD
and the control panel securely.
• Keep control and power cabling separated.
• DO NOT route the input and output cables
together.
• Insert an iron core in shielded cables.
EPCOS Filter
B84143A0036R105
B84143A0050R105
B84143A0066R105
B84143A0090R105
B84143A0120R105
B84143A0150R105
B84143B0250S020
B84143B0250S020
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
FLA @ 40° C
36
50
66
90
120
150
180
250
9

Advertisement