Toshiba W7 DN-57442-006 Installation & Operation Manual page 129

Adjustable speed drives
Table of Contents

Advertisement

Selection of Number of PG Input Phases
Program  Feedback  PG Settings
This parameter determines the type of information that is supplied by the
phase encoder.
Settings:
1 — Single Phase
2 — Two Phase
PG Disconnection Detection
Program  Feedback  PG Settings
This parameter Enables/Disables the system's monitoring of the PG
connection status when using encoders with line driver outputs.
Settings:
1 — Disabled
2 — Enabled
Electronic Gear Setting (pulses/rotation)
Program  Feedback  PG Settings
This parameter sets the number of pulses per revolution when using a
shaft-mounted encoder and the PG Option Board for closed loop speed
control.
Position Loop Gain
Program  Feedback  PG Settings
This parameter provides a divisor for the pulse input when operating in
the Pulse Control mode.
Position Completion Range
Program  Feedback  PG Settings
During a deceleration ramp, this parameter sets a speed range that must
be attained before the Stop command may be executed.
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Direct Access Number — F368
Parameter Type — Selection List
Factory Default — Two Phase
Changeable During Run — No
Direct Access Number — F369
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F370
Parameter Type — Numerical
Factory Default — 1000
Changeable During Run — Yes
Minimum — 100
Maximum — 4000
Direct Access Number — F371
Parameter Type — Numerical
Factory Default — 4.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Direct Access Number — F372
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 1
Maximum — 4000
F368-F372